Fire Extinguishers - NFPA-10 |
|
4-4.1
Frequency. Extinguishers shall be subject to maintenance not
more than one year apart or when specifically indicated by an inspection.
Maintenance procedures shall be performed in accordance with 4-4.2. |
| 4-4.1.3 Every six
years, stored pressure extinguishers that require a 12-year hydrostatic
test shall be emptied and subjected to the appropriate maintenance
procedures. When the applicable maintenance procedures are performed
during periodic recharging or hydrostatic testing, the six-year
requirement shall begin from that date.
|
|
Restaurant/Industrial Fire
Suppression Systems - NFPA 17, 17A, 96 |
|
3-3.1 At
least semi-annually, maintenance shall be conducted in accordance with the
manufacture's listed installation and maintenance manual. |
|
2-11.3 Fixed temperature
sensing elements of the fusible metal alloy type shall be replaced at least
annually or more frequently if necessary to assure proper operation of the
system.
|
|
Fire Sprinkler Systems -
NFPA 25 |
|
9-2.6 Main Drain Test.
A main
drain test shall be conducted quarterly at each system riser to determine if
there has been a change in the condition of the water supply piping and control
valves. |
|
9-2.7 Waterflow Alarm.
All
waterflow alarms shall be tested quarterly in accordance with the manufacture's
instructions. |
| 2-3.3.1 Testing the waterflow alarms
on wet pipe systems shall be accomplished by opening the inspector's test
connection.
|
|
Fire Alarm Systems - NFPA 72 |
| 7-3.2 Testing Testing shall be
performed in accordance with the schedules in this chapter or more frequently
where required by the authority having juristiction. Where automatic
testing is performed at least weekly by a remotely monitored fire alarm control
unit specifically listed for the application, the manual testing frequency shall
be permitted to be extended to annually.
|
|
Emergency & Exit Signs
& Lighting - NFPA 101 |
|
5-10.1.2
Exits shall be marked by an
approved sign readily visible from any direction of exit access. |
|
5-9.2.1
Emergency illumination
shall be provided for a period of 90 minutes in the event of failure of normal
lighting.
|
|
Hand Held Fire
Hose - NFPA 1962
|
2-3.3 In-service hose shall be
unracked, unreeled, or unrolled and physically inspected as specified in Section
2-5 at least annually. Hose shall be reracked, rereeled, or rerolled so
that any folds any folds do not occur at the same position on the hose.
|
| |